City of Battle Creek Sealed Solicitation
Title: AIR TRAFFIC CONTROL TOWER CHILLER REPLACEMENT PROJECT
Deadline: 1/24/2023 2:00 PM (UTC-05:00) Eastern Time (US & Canada)
Status: Deadline Expired
Solicitation Number: 2023-036B
Description: The City of Battle Creek will accept sealed bids for ATCT Chiller Replacement Project.
Topic: AIR TRAFFIC CONTROL TOWER CHILLER REPLACEMENT PROJECT BID OPENING
Time: Jan 24, 2023, 02:00 PM Eastern Time (US and Canada)
Join Zoom Meeting
https://us02web.zoom.us/j/81432284044
Meeting ID: 814 3228 4044
One tap mobile
+13092053325,,81432284044# US
+13126266799,,81432284044# US (Chicago)
Dial by your location
+1 309 205 3325 US
+1 312 626 6799 US (Chicago)
+1 646 931 3860 US
+1 929 205 6099 US (New York)
+1 301 715 8592 US (Washington DC)
+1 305 224 1968 US
+1 719 359 4580 US
+1 253 205 0468 US
+1 253 215 8782 US (Tacoma)
+1 346 248 7799 US (Houston)
+1 360 209 5623 US
+1 386 347 5053 US
+1 507 473 4847 US
+1 564 217 2000 US
+1 669 444 9171 US
+1 669 900 6833 US (San Jose)
+1 689 278 1000 US
Meeting ID: 814 3228 4044
Find your local number: https://us02web.zoom.us/u/kAibBYfGQ
Pre-Bid Meeting Date: 1/11/2023 2:00 PM
Pre-Bid Meeting Details: BC Executive Airport at Kellogg Field 15551 Airport Rd. Battle Creek, MI 49015 followed by walk-through
Documents:
Documents as of 12/15/2022 |
---|
Login to view documents |
Login to view documents |
PLANHOLDERS:
Date | Company Name |
---|---|
12/16/2022 4:39:41 AM | IMS |
12/16/2022 7:08:24 AM | Positive Trades Group |
12/16/2022 8:59:30 AM | Matrix Consulting Engineers, Inc. |
12/16/2022 11:09:04 AM | TowerPinkster |
12/16/2022 11:10:57 AM | Builders Exchange of Michigan |
12/19/2022 7:03:58 AM | Johnson & Wood, LLC |
12/19/2022 8:18:01 AM | Kalamazoo Builders Exchange |
12/27/2022 1:52:22 PM | Thayer Power & Communication Line Construction CO., LLC |
12/29/2022 2:35:39 PM | Seven Generations A+E |
1/4/2023 3:15:57 PM | Wightman |
1/6/2023 4:15:14 PM | IT Works! Inc. dba Volanno |
1/9/2023 6:44:20 PM | U. S. Healthcare Medical Supplies and Equipment LLC |
1/20/2023 2:23:32 AM | Dodge Data & Analytics |
1/20/2023 5:38:14 AM | ConstructConnect |
1/23/2023 12:08:08 PM | Carrier |
1/23/2023 3:17:28 PM | Process Engineering and Equipment CO |
1/23/2023 4:34:47 PM | C&J General contractors |
1/23/2023 4:48:40 PM | Advantage Mechanical Group |
1/23/2023 4:54:37 PM | dodge data and analytics |
1/24/2023 6:54:36 AM | Dodge Data |
1/24/2023 7:29:18 AM | Dodge Data & Analytics |
1/24/2023 7:38:10 AM | Monarch Welding & Engineering, Inc. |
1/24/2023 8:34:15 AM | Builders Exchange of Lansing |
1/24/2023 8:56:40 AM | Process Engineering & Equipment Co. |
1/24/2023 11:16:03 AM | Monarch Welding and Engineering |
1/24/2023 1:03:19 PM | Mall City Mechanical |
1/24/2023 1:10:00 PM | W Soule & Co |
1/24/2023 5:53:36 PM | Pro Services |
1/25/2023 1:36:45 PM | hunter-prell co. |
2/13/2023 1:28:42 PM | W Soule & Company |
Addition 1
Posted: 1/19/2023
Type of Addition: Addendum 1
Overview: The following changes, additions and deletions have been provided:
The following clarifications and changes shall be included in the Plans and Specifications for the above-referenced project, as prepared by Wightman & Associates, Inc. dated 11/18/2022. This Addendum shall be deemed a part of the Contract Documents, and to the extent that the provisions of the other Contract Documents are in conflict herewith, this Addendum shall control.
CLARIFICATIONS:
1. All final questions are to be directed to the architect by end of day 1/19/2023. Addendum No. 2 will be submitted 1/20/2023 if needed. gmonberg@gowightman.com or sholland@gowightman.com
2. If needed, a temporary full-system shutdown can be executed during off-hours and needs to be coordinated with the Air Traffic Control Tower maintenance personnel.
3. The chillers are a lead-lag system, and the new chillers are intended to be installed one at a time so that one chiller can remain running during construction.
4. A radio room inside the building needs to remain conditioned at all times. A temporary cooling solution may need to be incorporated during construction to keep the space conditioned properly.
5. General project communication will be between the contractor and Wightman. Site access inquiries will be directed to Charles first and then to Miles Weaver.
a. Charles Orr, cporr@battlecreekmi.gov, 269-966-3570
b. Miles Weaver, mhweaver@battlecreekmi.gov, 269-966-3355
6. The project scope includes everything shown on the drawings and written in the specifications.
7. The controls are included and expected to be executed in this contract. The existing system is and will remain Johnson Controls Metasys.
a. Johnson Controls, Kyle Bivins, kyle.j.bivins@ji.com, 608-512-8001
8. KML Chemicals is the chemical treatment company currently utilized at the building and it is preferred that it remain KML Chemicals for this project.
a. KML Chemicals, Johnny Heyboer, 616-401-3221
SPECIFICATIONS:
1. Section 23 62 13 Air Cooled Liquid Chiller; Part 2 Materials, 2.1 Manufacturers; Add paragraph B: “Carrier can be used for the bid option without the economizer, but not for the bid option with the economizer.”
DRAWINGS:
1. Sheet ME200 Mechanical Schedules, Notes & Diagrams: Mechanical equipment C-2 could be a Carrier product equivalent to the specified Trane unit.
PRE-BID SIGN IN SHEET:
1. The sign-in sheet for the Pre-Bid meeting below:
This addendum must be acknowledged on the Offer and Acceptance or Offer to Contract page of your bid/proposal or your bid/proposal may be deemed non-responsive.
Deadline: 1/24/2023 2:00 PM
Solicitation #: 2023-036B
Documents:
Addition 2
Posted: 1/23/2023
Type of Addition: Addendum 2
Overview: answering further questions, material part of contract.
Documents:
Addition 3
Posted: 1/23/2023
Type of Addition: Addendums 3 and 4
Overview: The following changes, additions and deletions have been provided:
The Iran Sanctions form has been added to the bid documents. This is required by the Michigan IRAN ECONOMIC SANCTIONS ACT 517 of 2012.
The Familial Disclosure form is only required under Michigan Law for public school projects, not city or village work. It will not be required for this bid. Please disregard this item on the checklist.
PROJECT: Air Traffic Control Tower – Chiller Replacement
CLIENT: City of Battle Creek
ISSUE DATE: January 23, 2023
The following clarifications and changes shall be included in the Plans and Specifications for the above-referenced project, as prepared by Wightman & Associates, Inc. dated 11/18/2022. This Addendum shall be deemed a part of the Contract Documents, and to the extent that the provisions of the other Contract Documents are in conflict herewith, this Addendum shall control.
CLARIFICATIONS:
1. Remove the old chiller from the existing BMS. Add new chillers to the existing BMS. Where points overlap between the new chillers and existing chillers, the points shall be approached as new equipment. For example, if the alternate with the economizer coil is selected, some points associated with this alternate are not present in the existing system.
2. The primary pump VFD’s and associated points shall be added. Primary pump points are listed with the chiller control points. The VFD controls contractor shall provide multiple points to be pulled off the controller. The contractor shall coordinate with the owner for all information to be displayed and logged with the system. At a minimum, the alarms, status, RPM, and Hz shall be displayed and logged. The contractor shall note any other information to the owner that can be displayed for troubleshooting the system.
3. Omit the reference to the “Bid Form: Familial Disclosure Statement.”
4. Add the attached “Iran Affidavit of Compliance Form” to the Bid Form.
Deadline: 1/24/2023 2:00 PM
Solicitation #: 2023-036B
Documents:
Posted: 1/19/2023
Type of Addition: Addendum 1
Overview: The following changes, additions and deletions have been provided:
The following clarifications and changes shall be included in the Plans and Specifications for the above-referenced project, as prepared by Wightman & Associates, Inc. dated 11/18/2022. This Addendum shall be deemed a part of the Contract Documents, and to the extent that the provisions of the other Contract Documents are in conflict herewith, this Addendum shall control.
CLARIFICATIONS:
1. All final questions are to be directed to the architect by end of day 1/19/2023. Addendum No. 2 will be submitted 1/20/2023 if needed. gmonberg@gowightman.com or sholland@gowightman.com
2. If needed, a temporary full-system shutdown can be executed during off-hours and needs to be coordinated with the Air Traffic Control Tower maintenance personnel.
3. The chillers are a lead-lag system, and the new chillers are intended to be installed one at a time so that one chiller can remain running during construction.
4. A radio room inside the building needs to remain conditioned at all times. A temporary cooling solution may need to be incorporated during construction to keep the space conditioned properly.
5. General project communication will be between the contractor and Wightman. Site access inquiries will be directed to Charles first and then to Miles Weaver.
a. Charles Orr, cporr@battlecreekmi.gov, 269-966-3570
b. Miles Weaver, mhweaver@battlecreekmi.gov, 269-966-3355
6. The project scope includes everything shown on the drawings and written in the specifications.
7. The controls are included and expected to be executed in this contract. The existing system is and will remain Johnson Controls Metasys.
a. Johnson Controls, Kyle Bivins, kyle.j.bivins@ji.com, 608-512-8001
8. KML Chemicals is the chemical treatment company currently utilized at the building and it is preferred that it remain KML Chemicals for this project.
a. KML Chemicals, Johnny Heyboer, 616-401-3221
SPECIFICATIONS:
1. Section 23 62 13 Air Cooled Liquid Chiller; Part 2 Materials, 2.1 Manufacturers; Add paragraph B: “Carrier can be used for the bid option without the economizer, but not for the bid option with the economizer.”
DRAWINGS:
1. Sheet ME200 Mechanical Schedules, Notes & Diagrams: Mechanical equipment C-2 could be a Carrier product equivalent to the specified Trane unit.
PRE-BID SIGN IN SHEET:
1. The sign-in sheet for the Pre-Bid meeting below:
This addendum must be acknowledged on the Offer and Acceptance or Offer to Contract page of your bid/proposal or your bid/proposal may be deemed non-responsive.
Deadline: 1/24/2023 2:00 PM
Solicitation #: 2023-036B
Documents:
Posted: 1/23/2023
Type of Addition: Addendum 2
Overview: answering further questions, material part of contract.
Documents:
Posted: 1/23/2023
Type of Addition: Addendums 3 and 4
Overview: The following changes, additions and deletions have been provided:
The Iran Sanctions form has been added to the bid documents. This is required by the Michigan IRAN ECONOMIC SANCTIONS ACT 517 of 2012.
The Familial Disclosure form is only required under Michigan Law for public school projects, not city or village work. It will not be required for this bid. Please disregard this item on the checklist.
PROJECT: Air Traffic Control Tower – Chiller Replacement
CLIENT: City of Battle Creek
ISSUE DATE: January 23, 2023
The following clarifications and changes shall be included in the Plans and Specifications for the above-referenced project, as prepared by Wightman & Associates, Inc. dated 11/18/2022. This Addendum shall be deemed a part of the Contract Documents, and to the extent that the provisions of the other Contract Documents are in conflict herewith, this Addendum shall control.
CLARIFICATIONS:
1. Remove the old chiller from the existing BMS. Add new chillers to the existing BMS. Where points overlap between the new chillers and existing chillers, the points shall be approached as new equipment. For example, if the alternate with the economizer coil is selected, some points associated with this alternate are not present in the existing system.
2. The primary pump VFD’s and associated points shall be added. Primary pump points are listed with the chiller control points. The VFD controls contractor shall provide multiple points to be pulled off the controller. The contractor shall coordinate with the owner for all information to be displayed and logged with the system. At a minimum, the alarms, status, RPM, and Hz shall be displayed and logged. The contractor shall note any other information to the owner that can be displayed for troubleshooting the system.
3. Omit the reference to the “Bid Form: Familial Disclosure Statement.”
4. Add the attached “Iran Affidavit of Compliance Form” to the Bid Form.
Deadline: 1/24/2023 2:00 PM
Solicitation #: 2023-036B
Documents: