Title: 23-DES-ITBPW-620 Interior Renovation of AED Floor
Deadline: 6/21/2023 3:30 PM (UTC-05:00) Eastern Time (US & Canada)
Status: Awarded
Solicitation Number: 23-DES-ITBPW-620
Description: AED CURRENTLY OCCUPIES THE ENTIRE 15TH FLOOR – 11,132 TOTAL SQUARE. RENOVATION IS APPROXIMATELY 4,200 SF. OF THIS FLOOR. THE REMAINING FLOOR AREA WILL BE OCCUPIED DAILY BY GENERAL OFFICE WORKERS DURING NORMAL BUSINESS HOURS. RENOVATION SHALL INCLUDE, BUT NOT BE LIMITED TO, PROVIDING FOR OPEN OFFICE AREAS, MEETING ROOM, ACCESSORY STORAGE SPACE REPLACEMENT OF FINISHES, EQUIPMENT/IT SUPPORT AND OTHER DEVICES, RE-BALANCING OF HVAC AIR FLOW
Pre-Bid Meeting Date: 6/6/2023 10:00 AM
Documents:
Addition 1
Posted: 6/6/2023
Type of Addition: Attendance Sheet & Minutes
Documents:
Question 1
Posted: 6/13/2023
Question: When it comes to the mural, do you have a designated person to proceed with? Also, what finish does the wall need in case they are painting or pasting the mural?
Response: Owner to provide artwork for mural. Contractor to provide Level 4 finish, wall to receive Owner provided mural. Contractor to paint wall PT-4, at no additional cost, should Owner not install mural.
Question 2
Posted: 6/13/2023
Question: When it comes to the South of Corridor 15V22, on AF101, it says the wall should have PT-2, but on A301.3, it asks for PT-5 on the wall. Which one should we use for that wall above the Wainscot?
Response: On AF101 – PT-2 is only at the inside face of wall. For finish of south wall in Corridor 15V22, per detail 3/A301, wall above wainscot to be PT-5. Also shown in this detail, the angled, inside face of wall is to be painted PT-2.On AF101 – PT-2 is only at the inside face of wall. For finish of south wall in Corridor 15V22, per detail 3/A301, wall above wainscot to be PT-5. Also shown in this detail, the angled, inside face of wall is to be painted PT-2.
Question 3
Posted: 6/13/2023
Question: When it comes to paint coverage in the Catering Pantry, does it involve just the pantry area or does it include the hallway connection going North?
Response: Paint is to be provided in the entire corridor.
Question 4
Posted: 6/13/2023
Question: Is there going to be on-site storage for materials that need to be moved and reinstalled after work is complete?
Response: Storage on-site will be limited to the area of work in Suite 1500.
Question 5
Posted: 6/13/2023
Question: Should we carry an allowance for obstructions above the ceiling in conference room prohibiting the install of wood slats?
Response: Contractor to install wood slats as shown in location where existing ceiling is located
Question 6
Posted: 6/13/2023
Question: Are we to provide toilet facilities?
Response: See response # 2 in Addendum #1
Question 7
Posted: 6/13/2023
Question: We assume that the owner is keying the cores for the doors?
Response: READ all the solicitation documents carefully for information about keying of the door.
Question 8
Posted: 6/13/2023
Question: Is there a controls contractor connected to this project?
Response: See response to # 1 in Addendum #1.. READ the Landlord’s Construction Rules and Regulations carefully
Question 9
Posted: 6/13/2023
Question: Can we put a dumpster on-site?
Response: READ solicitation documents carefully, including the Landlord’s Construction Rules & Regulations. If you need to place the dumpster on the street near the curb. You will need to apply for a permit to do so
Question 10
Posted: 6/13/2023
Question: Will someone be removing the furniture out of the rooms?
Response: Yes, furniture will be remove by others except in conference rooms 15W15 & 15W12. The contractor will need to move the furniture around to replace the carpet in these rooms
Question 11
Posted: 6/13/2023
Question: We assume that a designated elevator can be used during normal work hours for delivery of materials?
Response: This is correct, only the freight elevator will be used by the contractor
Question 12
Posted: 6/13/2023
Question: Should we put in an allowance for spray on fire protection?
Response: Sprayed fire resistive materials are to be provided for any new structural supports and for touch-up of any damaged areas during construction to match existing construction. Contractor to provide the required fire protection based on scope of work.
Question 13
Posted: 6/13/2023
Question: Please see PWC Companies RFIs below: 1. Please define the layout pattern for both CPT-1 & CPT-2.OPTIONS; monolithic, half lap, brick ashlar, basket weave, plank half lap, monolithic stepping, random or herringbone. 2. Please define the type of base (RB-1) should be. Tarkett / Johnsonite makes several types of rubber millwork, vinyl, & rubber cove or toeless. 3. Please define transitions at all doors going into existing spaces. 4. Can you please provide details of Loading dock elevator dimension (i.e. W x H Opening, WxDxH inside Elevator)? 5. Can you please clarify if the opening the door uses Floor Hinge or overhead? If Floor Hinges, what is the thickness of concrete slab? 6. Can you please clarify if regular clear glass or low iron glass should be used? 7. Can you please provide the color of hardware (i.e. Brushed Stainless , Matte Back)? 8. Please clarify if there are BMS controls for this project.
Response: 1. CPT-1 and CPT-2 should be installed in Brick Ashlar pattern. 2. Per Specification Section 09 6513 provide base style RB-1 per section 2.1.B.2 depending on the flooring material. 3. At new carpet to existing carpet, no transition strip to be provided. Contractor to install new carpet, cut clean and butt tight to existing carpet. Transition to occur at centerline of door when door is closed. At locations where marble rot stone sill is existing, sill to remain and new carpet to butt up to existing sill. At locations where transition to concrete, provide rubber reducer strip. 4. The Loading Dock can be seen and access from the side street. You should go to the building site to determine the loading dock dimensions. The freight elevator is similar size as all the passenger elevators. 5. It is not clear what door this is referencing. Refer to the specifications for all door hardware. 6. Contractor to provide low iron glass. 7. All door hardware finishes are to match existing building finishes. Refer to door schedule for door hardware finishes. 8. READ the solicitation documents carefully, including the Landlord’s Construction Rules & Regulations.
Posted: 6/13/2023
Question: When it comes to the mural, do you have a designated person to proceed with? Also, what finish does the wall need in case they are painting or pasting the mural?
Response: Owner to provide artwork for mural. Contractor to provide Level 4 finish, wall to receive Owner provided mural. Contractor to paint wall PT-4, at no additional cost, should Owner not install mural.
Posted: 6/13/2023
Question: When it comes to the South of Corridor 15V22, on AF101, it says the wall should have PT-2, but on A301.3, it asks for PT-5 on the wall. Which one should we use for that wall above the Wainscot?
Response: On AF101 – PT-2 is only at the inside face of wall. For finish of south wall in Corridor 15V22, per detail 3/A301, wall above wainscot to be PT-5. Also shown in this detail, the angled, inside face of wall is to be painted PT-2.On AF101 – PT-2 is only at the inside face of wall. For finish of south wall in Corridor 15V22, per detail 3/A301, wall above wainscot to be PT-5. Also shown in this detail, the angled, inside face of wall is to be painted PT-2.
Posted: 6/13/2023
Question: When it comes to paint coverage in the Catering Pantry, does it involve just the pantry area or does it include the hallway connection going North?
Response: Paint is to be provided in the entire corridor.
Posted: 6/13/2023
Question: Is there going to be on-site storage for materials that need to be moved and reinstalled after work is complete?
Response: Storage on-site will be limited to the area of work in Suite 1500.
Posted: 6/13/2023
Question: Should we carry an allowance for obstructions above the ceiling in conference room prohibiting the install of wood slats?
Response: Contractor to install wood slats as shown in location where existing ceiling is located
Posted: 6/13/2023
Question: Are we to provide toilet facilities?
Response: See response # 2 in Addendum #1
Posted: 6/13/2023
Question: We assume that the owner is keying the cores for the doors?
Response: READ all the solicitation documents carefully for information about keying of the door.
Posted: 6/13/2023
Question: Is there a controls contractor connected to this project?
Response: See response to # 1 in Addendum #1.. READ the Landlord’s Construction Rules and Regulations carefully
Posted: 6/13/2023
Question: Can we put a dumpster on-site?
Response: READ solicitation documents carefully, including the Landlord’s Construction Rules & Regulations. If you need to place the dumpster on the street near the curb. You will need to apply for a permit to do so
Posted: 6/13/2023
Question: Will someone be removing the furniture out of the rooms?
Response: Yes, furniture will be remove by others except in conference rooms 15W15 & 15W12. The contractor will need to move the furniture around to replace the carpet in these rooms
Posted: 6/13/2023
Question: We assume that a designated elevator can be used during normal work hours for delivery of materials?
Response: This is correct, only the freight elevator will be used by the contractor
Posted: 6/13/2023
Question: Should we put in an allowance for spray on fire protection?
Response: Sprayed fire resistive materials are to be provided for any new structural supports and for touch-up of any damaged areas during construction to match existing construction. Contractor to provide the required fire protection based on scope of work.
Posted: 6/13/2023
Question: Please see PWC Companies RFIs below: 1. Please define the layout pattern for both CPT-1 & CPT-2.OPTIONS; monolithic, half lap, brick ashlar, basket weave, plank half lap, monolithic stepping, random or herringbone. 2. Please define the type of base (RB-1) should be. Tarkett / Johnsonite makes several types of rubber millwork, vinyl, & rubber cove or toeless. 3. Please define transitions at all doors going into existing spaces. 4. Can you please provide details of Loading dock elevator dimension (i.e. W x H Opening, WxDxH inside Elevator)? 5. Can you please clarify if the opening the door uses Floor Hinge or overhead? If Floor Hinges, what is the thickness of concrete slab? 6. Can you please clarify if regular clear glass or low iron glass should be used? 7. Can you please provide the color of hardware (i.e. Brushed Stainless , Matte Back)? 8. Please clarify if there are BMS controls for this project.
Response: 1. CPT-1 and CPT-2 should be installed in Brick Ashlar pattern. 2. Per Specification Section 09 6513 provide base style RB-1 per section 2.1.B.2 depending on the flooring material. 3. At new carpet to existing carpet, no transition strip to be provided. Contractor to install new carpet, cut clean and butt tight to existing carpet. Transition to occur at centerline of door when door is closed. At locations where marble rot stone sill is existing, sill to remain and new carpet to butt up to existing sill. At locations where transition to concrete, provide rubber reducer strip. 4. The Loading Dock can be seen and access from the side street. You should go to the building site to determine the loading dock dimensions. The freight elevator is similar size as all the passenger elevators. 5. It is not clear what door this is referencing. Refer to the specifications for all door hardware. 6. Contractor to provide low iron glass. 7. All door hardware finishes are to match existing building finishes. Refer to door schedule for door hardware finishes. 8. READ the solicitation documents carefully, including the Landlord’s Construction Rules & Regulations.