Lindbergh Schools Sealed Solicitation

Title: Secure Entries at Kennerly Elementary & Truman Middle School

Deadline: 3/30/2021 2:00 PM   (UTC-06:00) Central Time (US & Canada)

Status: Awarded

Description: Secure entries at both Kennerly Elementary School and Truman Middle School. Qualified bidders are invited to submit bids for this project as described in the attached documents. 


Pre-Bid Meeting Date: 3/17/2021 10:00 AM

Pre-Bid Meeting Details: Please sign up if you plan to attend the pre-bid meeting.Pre-Bid Meeting will be a zoom virtual meeting.


Documents:

Documents as of 3/8/2021
Login to view documents
Login to view documents
Login to view documents
Login to view documents
Login to view documents
Login to view documents
Login to view documents
Addition 1

Posted: 3/24/2021

Type of Addition: #2 Question Response 3/24/21

Overview:



  1. D20/AD1.01T on plan, but not on legend. Please clarify.

Keynote D20 should read: SAWCUT PORTION OF STEEL TUBES FROM SOUTH CANOPY TO REMAIN 

  1. Explain arrow from D18/AD1.01T. Seems like this room ceiling is to be demolished, but arrow runs outside of this room.

The ceiling should be demolished in the existing nurses suite and nurse’s restroom ( the areas directly to the left of the existing stairs) and the existing classroom (the area directly to the right of the existing stairs). 

  1. Is there plywood on the underside of the new exterior canopy? 4/A4.01T shows a portion of plywood, but none shown anywhere else on the drawings. RCP does not show any portion of this overhang.

Yes. Please note the plywood sheathing in detail 7/A4.01-T and 2/A4.01-T as well. 

  1. N1 and N2 door hardware notes...why are we trying to save, modify, patch and reuse frames and/or doors here? Can these be changed to new openings?

We could replace the doors with a Narrow Light 20 Minute Fire Rated Door however, we would highly suggest keeping the frames as they are grouted in. Frames will need to be patched, repaired, and repainted. 

  1. 1/A9.12T - underside of canopy says NO WORK. 2 & 3 on A2.01T says to repaint existing canopy decking. Which is correct?

Repaint existing canopy decking. 

  1. Confirm status of addendums issued to date and forthcoming. Vendor Registry page seems to say the reissued spec manual is an "addendum," but do not see anything like we normally do when an addendum is issued with number and date. Clarify so we can correctly modify our bid form.

Through the VR process the day following the question deadline a listing of all the " LIST OF DATA SHARED SUBSEQUENT TO ORIGINAL SPECS" .  We will add number and date to each item for this project.  We will update our process to make sure a number and date is included each time a subsequent date is shared and posted to the site.   7. Several glazing types labeled, but do not correlate with storefront elevations. Please clarify.
The glazing indicated on the Glazing Types Legend on A1.41-T notates both glazing for the storefront elevations and also glazing for door types and the transaction window.



Addition 2

Posted: 3/26/2021

Type of Addition: Addendum No.1

Overview: Please see the attached document. 

Documents:

Addition 3

Posted: 3/29/2021

Type of Addition: Summary of Additional Information: 1 Addendum and Questions

Overview:

Questions asked during the bid process and the responses that were given. 

 

3/18/2021

  1. At Kennerly, are the windows in the office area (W5, W6, W7, and W8) going to be aluminum/storefront material or hollow metal frames?                                                                      It would be hollow metal framing.

3/23/2021

  1. D20/AD1.01T on plan, but not on legend. Please clarify.

Keynote D20 should read: SAWCUT PORTION OF STEEL TUBES FROM SOUTH CANOPY TO REMAIN

 

  1. Explain arrow from D18/AD1.01T. Seems like this room ceiling is to be demolished, but arrow runs outside of this room.

The ceiling should be demolished in the existing nurses suite and nurse’s restroom ( the areas directly to the left of the existing stairs) and the existing classroom (the area directly to the right of the existing stairs).

 

  1. Is there plywood on the underside of the new exterior canopy? 4/A4.01T shows a portion of plywood, but none shown anywhere else on the drawings. RCP does not show any portion of this overhang.

Yes. Please note the plywood sheathing in detail 7/A4.01-T and 2/A4.01-T as well.

 

  1. N1 and N2 door hardware notes...why are we trying to save, modify, patch and reuse frames and/or doors here? Can these be changed to new openings?

We could replace the doors with a Narrow Light 20 Minute Fire Rated Door however, we would highly suggest keeping the frames as they are grouted in. Frames will need to be patched, repaired, and repainted.

 

  1. 1/A9.12T - underside of canopy says NO WORK. 2 & 3 on A2.01T says to repaint existing canopy decking. Which is correct?

Repaint existing canopy decking.

 

  1. Confirm status of addendums issued to date and forthcoming. Vendor Registry page seems to say the reissued spec manual is an "addendum," but do not see anything like we normally do when an addendum is issued with number and date. Clarify so we can correctly modify our bid form.

Through the VR process the day following the question deadline a listing of all the " LIST OF DATA SHARED SUBSEQUENT TO ORIGINAL SPECS" .  We will add a number and date to each item for this project.  We will update our process to make sure a number and date is included each time a subsequent date is shared and posted to the site. 

 

  1. Several glazing types labeled, but do not correlate with storefront elevations. Please clarify.
    The glazing indicated on the Glazing Types Legend on A1.41-T notates both glazing for the storefront elevations and also glazing for door types and the transaction window.


Documents:

Addition 4

Posted: 3/30/2021

Type of Addition: Link to Virtual Bid Opening for Kennerly & Truman Secure Entries

Overview:

Tuesday,  March 30, 2021 2pm – 3:30pm (CDT)
Join Zoom Meeting
https://zoom.us/j/94236042263?pwd=SlhMUnYvUGkxQXNOK1o5K3I1R1N3dz09

Meeting ID: 942 3604 2263
Passcode: 896522
One tap mobile
+13126266799,,94236042263#,,,,*896522# US (Chicago)
+16468769923,,94236042263#,,,,*896522# US (New York)

Dial by your location
        +1 312 626 6799 US (Chicago)
        +1 646 876 9923 US (New York)
        +1 301 715 8592 US (Washington DC)
        +1 346 248 7799 US (Houston)
        +1 408 638 0968 US (San Jose)
        +1 669 900 6833 US (San Jose)
        +1 253 215 8782 US (Tacoma)
Meeting ID: 942 3604 2263
Passcode: 896522
Find your local number: https://zoom.us/u/abuObrOIv2





Addition 5

Posted: 3/30/2021

Type of Addition: In Review

Addition 6

Posted: 4/21/2021

Type of Addition: Award Information

Overview: Wachter, Inc

Amount: $1,267,200.00

Question 1

Posted: 3/18/2021

Question: At Kennerly, are the windows in the office area (W5, W6, W7, and W8) going to be aluminum/storefront material or hollow metal frames?

Response: It would be hollow metal framing.

Question 2

Posted: 3/23/2021

Question: Regarding Truman; 1. D20/AD1.01T on plan, but not on legend. Please clarify. 2. Explain arrow from D18/AD1.01T. Seems like this room ceiling is to be demolished, but arrow runs outside of this room. 3. Is there plywood on the underside of the new exterior canopy? 4/A4.01T shows a portion of plywood, but none shown anywhere else on the drawings. RCP does not show any portion of this overhang. 4. N1 and N2 door hardware notes...why are we trying to save, modify, patch and reuse frames and/or doors here? Can these be changed to new openings? 5. 1/A9.12T - underside of canopy says NO WORK. 2 & 3 on A2.01T says to repaint existing canopy decking. Which is correct? 6. Confirm status of addendums issued to date and forthcoming. Vendor Registry page seems to say the reissued spec manual is an "addendum," but do not see anything like we normally do when an addendum is issued with number and date. Clarify so we can correctly modify our bid form. 7. Several glazing types labeled, but do not correlate with storefront elevations. Please clarify.

Response: Please see responses listed under Additions

Posted: 3/24/2021

Type of Addition: #2 Question Response 3/24/21

Overview:



  1. D20/AD1.01T on plan, but not on legend. Please clarify.

Keynote D20 should read: SAWCUT PORTION OF STEEL TUBES FROM SOUTH CANOPY TO REMAIN 

  1. Explain arrow from D18/AD1.01T. Seems like this room ceiling is to be demolished, but arrow runs outside of this room.

The ceiling should be demolished in the existing nurses suite and nurse’s restroom ( the areas directly to the left of the existing stairs) and the existing classroom (the area directly to the right of the existing stairs). 

  1. Is there plywood on the underside of the new exterior canopy? 4/A4.01T shows a portion of plywood, but none shown anywhere else on the drawings. RCP does not show any portion of this overhang.

Yes. Please note the plywood sheathing in detail 7/A4.01-T and 2/A4.01-T as well. 

  1. N1 and N2 door hardware notes...why are we trying to save, modify, patch and reuse frames and/or doors here? Can these be changed to new openings?

We could replace the doors with a Narrow Light 20 Minute Fire Rated Door however, we would highly suggest keeping the frames as they are grouted in. Frames will need to be patched, repaired, and repainted. 

  1. 1/A9.12T - underside of canopy says NO WORK. 2 & 3 on A2.01T says to repaint existing canopy decking. Which is correct?

Repaint existing canopy decking. 

  1. Confirm status of addendums issued to date and forthcoming. Vendor Registry page seems to say the reissued spec manual is an "addendum," but do not see anything like we normally do when an addendum is issued with number and date. Clarify so we can correctly modify our bid form.

Through the VR process the day following the question deadline a listing of all the " LIST OF DATA SHARED SUBSEQUENT TO ORIGINAL SPECS" .  We will add number and date to each item for this project.  We will update our process to make sure a number and date is included each time a subsequent date is shared and posted to the site.   7. Several glazing types labeled, but do not correlate with storefront elevations. Please clarify.
The glazing indicated on the Glazing Types Legend on A1.41-T notates both glazing for the storefront elevations and also glazing for door types and the transaction window.



Posted: 3/26/2021

Type of Addition: Addendum No.1

Overview: Please see the attached document. 

Documents:

Posted: 3/29/2021

Type of Addition: Summary of Additional Information: 1 Addendum and Questions

Overview:

Questions asked during the bid process and the responses that were given. 

 

3/18/2021

  1. At Kennerly, are the windows in the office area (W5, W6, W7, and W8) going to be aluminum/storefront material or hollow metal frames?                                                                      It would be hollow metal framing.

3/23/2021

  1. D20/AD1.01T on plan, but not on legend. Please clarify.

Keynote D20 should read: SAWCUT PORTION OF STEEL TUBES FROM SOUTH CANOPY TO REMAIN

 

  1. Explain arrow from D18/AD1.01T. Seems like this room ceiling is to be demolished, but arrow runs outside of this room.

The ceiling should be demolished in the existing nurses suite and nurse’s restroom ( the areas directly to the left of the existing stairs) and the existing classroom (the area directly to the right of the existing stairs).

 

  1. Is there plywood on the underside of the new exterior canopy? 4/A4.01T shows a portion of plywood, but none shown anywhere else on the drawings. RCP does not show any portion of this overhang.

Yes. Please note the plywood sheathing in detail 7/A4.01-T and 2/A4.01-T as well.

 

  1. N1 and N2 door hardware notes...why are we trying to save, modify, patch and reuse frames and/or doors here? Can these be changed to new openings?

We could replace the doors with a Narrow Light 20 Minute Fire Rated Door however, we would highly suggest keeping the frames as they are grouted in. Frames will need to be patched, repaired, and repainted.

 

  1. 1/A9.12T - underside of canopy says NO WORK. 2 & 3 on A2.01T says to repaint existing canopy decking. Which is correct?

Repaint existing canopy decking.

 

  1. Confirm status of addendums issued to date and forthcoming. Vendor Registry page seems to say the reissued spec manual is an "addendum," but do not see anything like we normally do when an addendum is issued with number and date. Clarify so we can correctly modify our bid form.

Through the VR process the day following the question deadline a listing of all the " LIST OF DATA SHARED SUBSEQUENT TO ORIGINAL SPECS" .  We will add a number and date to each item for this project.  We will update our process to make sure a number and date is included each time a subsequent date is shared and posted to the site. 

 

  1. Several glazing types labeled, but do not correlate with storefront elevations. Please clarify.
    The glazing indicated on the Glazing Types Legend on A1.41-T notates both glazing for the storefront elevations and also glazing for door types and the transaction window.


Documents:

Posted: 3/30/2021

Type of Addition: Link to Virtual Bid Opening for Kennerly & Truman Secure Entries

Overview:

Tuesday,  March 30, 2021 2pm – 3:30pm (CDT)
Join Zoom Meeting
https://zoom.us/j/94236042263?pwd=SlhMUnYvUGkxQXNOK1o5K3I1R1N3dz09

Meeting ID: 942 3604 2263
Passcode: 896522
One tap mobile
+13126266799,,94236042263#,,,,*896522# US (Chicago)
+16468769923,,94236042263#,,,,*896522# US (New York)

Dial by your location
        +1 312 626 6799 US (Chicago)
        +1 646 876 9923 US (New York)
        +1 301 715 8592 US (Washington DC)
        +1 346 248 7799 US (Houston)
        +1 408 638 0968 US (San Jose)
        +1 669 900 6833 US (San Jose)
        +1 253 215 8782 US (Tacoma)
Meeting ID: 942 3604 2263
Passcode: 896522
Find your local number: https://zoom.us/u/abuObrOIv2





Posted: 3/30/2021

Type of Addition: In Review

Posted: 4/21/2021

Type of Addition: Award Information

Overview: Wachter, Inc

Amount: $1,267,200.00

Posted: 3/18/2021

Question: At Kennerly, are the windows in the office area (W5, W6, W7, and W8) going to be aluminum/storefront material or hollow metal frames?

Response: It would be hollow metal framing.

Posted: 3/23/2021

Question: Regarding Truman; 1. D20/AD1.01T on plan, but not on legend. Please clarify. 2. Explain arrow from D18/AD1.01T. Seems like this room ceiling is to be demolished, but arrow runs outside of this room. 3. Is there plywood on the underside of the new exterior canopy? 4/A4.01T shows a portion of plywood, but none shown anywhere else on the drawings. RCP does not show any portion of this overhang. 4. N1 and N2 door hardware notes...why are we trying to save, modify, patch and reuse frames and/or doors here? Can these be changed to new openings? 5. 1/A9.12T - underside of canopy says NO WORK. 2 & 3 on A2.01T says to repaint existing canopy decking. Which is correct? 6. Confirm status of addendums issued to date and forthcoming. Vendor Registry page seems to say the reissued spec manual is an "addendum," but do not see anything like we normally do when an addendum is issued with number and date. Clarify so we can correctly modify our bid form. 7. Several glazing types labeled, but do not correlate with storefront elevations. Please clarify.

Response: Please see responses listed under Additions