County of Escambia Quote

Title: Escambia County Boiler PM

Deadline: 11/5/2021 12:00 PM   (UTC-06:00) Central Time (US & Canada)

Status: Deadline Expired

Quote Number: FMBOILERPMRF

Description:

Escambia County Facilities Boiler PM

 

This scope of work is for a full annual preventive maintenance and efficiency check/calibration of 14ea hydronic boiler located in various buildings within Escambia County Florida. This work is to also include proposals for any necessary repairs that pose an immediate safety concern. The PMs are to be performed during normal working hours with little or no disruption to the buildings being served. Below are the listed minimum requirements that must be completed:

  • Full schedule of date and time work will be performed, due to escorts from Escambia County Facilities Department must be available for building access.

  • Remove and clean burners.

  • Remove and clean pilot assembly and flame rectifier.

  • Clean heat exchanger.

  • Re-install boiler components.

  • Start-up boiler.

  • Check and adjust manifold gas pressure.

  • Check limit and safety controls. Adjust for safe and proper operation, according to the boiler

    manufacturer’s specifications. Any safeties found to be “bypassed” must be reconnected and functional.

  • Check make-up water system for proper operation.

  • Check and repair all indicator lights to insure they are fully operational.

  • Check/clean blowers/fans if applicable.

  • Conduct combustion test at full fire. Adjust for proper operation and efficiency.

  • Check the operation of the safety pressure relief valve.

  • Remove all maintenance debris and tools from site. Clean work area.

  • Prepare basic report of service performed on each boiler (CO 2, CO, W.C.

    gas pressure, building supply water temperatures and stack temperature)

     

 

Ordin-Orvis      201 South Palafox Street                                               Proposal amount  $__________

(5)  Boilers       Make: RBI        Model # DB1950

 

MC Blanchard     190 Governmental Center                                           Proposal amount  $__________

(3)  Boilers       Make: Raypak        Model # H9-2342B

 

 

Sheriff Administration Office    1700 West Leonard Street                     Proposal amount  $__________

(2) Boilers        Make: Raypak        Model # H92072

 

Road Prison Barracks    601 Highway 297A                                          Proposal amount  $__________

(1) Boiler          Make: Raypak        Model # 1125C

(1) Boiler          Make: Sellers Eng. Model# BT-80-1000

 

Animal Shelter    200 West Fairfield Drive                                             Proposal amount  $__________

(1) Boiler          Make: Weil-McClain        Model # PFG-65PN

 

Juvenile Justice Center     1800 Saint Marys Avenue                               Proposal amount  $__________

(1) Boiler          Make: Raypak        Model # H3-1631

 

For more information, Please contact Bill Barrett @ 850-595-4634 or 850-554-2723